HYBO SERIES TS
100 - 500 Kw
Built-In Transformer
Technical DataHYBO 100 TSHYBO 150 TSHYBO 250 TSHYBO 500 TS
Battery 
Battery Voltage Range ( V )420-850420 – 850420-850500 – 850
Max . Charge / Discharge Current ( A )2704056731128
AC Output ( On Grid ) 
Max . AC Output Power ( KVA )110165275550
Rated Output Power ( kW )100150250500
Rated Voltage ( Vac )400
Voltage Range ( Vac )320 – 460
Rated Output Current ( A )144216361722
Max . Output Current ( A )159238397794
Rated Frequency ( Hz )50 / 60
Frequency Range ( Hz )45-55 / 55-65
THDI< 3 %
Power Factor1 Lead – 1 Lag ( Configurable )
AC Format3W + N + PE
AC Output ( Off Grid ) 
Rated Voltage ( Vac )400
THDU< 1 % Linear , < 1 % Nonlinear
Rated Frequency ( Hz )50 / 60
Overload Ability110 % Long – term
General Data 
Max . Efficiency97.1 %97.1 %97.30 %97.50 %
IP RatingIP21
Noise ( dB )< 70
Ambient Temperature-30 ° C ~ +55 ° C
Cooling MethodForced Air Cooling
Relative Humidity0-95 % non – Condensing
Altitude3000m ( Up to 5000m with derating )
Size ( W x D x H ) ( mm )800 × 800 × 2050800 x 800 × 20501200 x 800 x 20501600 × 1050 x 2050
Weight ( kg )936105715822665
Transformation Ratio270 / 400270 / 400270 / 400315/400
Shutdown Self Consumption ( W )< 100
ON / OFF Grid Transfer TimeAutomatic / Seamsless
Display And Communication 
DisplayLCD
BMS CommunicationRS485 , CAN
EMS CommunicationRS485 , TCP / IP
StandardsIEC / EN 62109-1 / -2, IEC / EN 62477-1,
IEC / EN 61000-6-2, IEC / EN 61000-4, CGC
*NSR 097 / CEI 016 / VDE ( On-Going )

See warranty for performance warranty applicability.
See Performance Warranty Terms and the Standard Test Conditions “STC”.
All data is subjected to change without prior notice: Always ask WeCo for the most recent datasheet and manual before purchasing.
No part of this document can be copied or reproducted without WeCo written permission.

HYBO SERIES CS
100 - 500 Kw
Built-In Transformer
HYBO CS Buck mode HYBRID HYBO BUILT IN TRANSFORMER
PV Buck Mode
Model CS100 CS150 CS250 CS500
On Grid AC specifications
Max. Output power (kVA) 110 165 275 550
Rated Output Power (kW) 100 150 250 500
Rated Voltage (V) 400
Voltage Range (V) 320~460
Rated Current (A) 144 216 361 722
Rated Frequency (Hz) 50 / 60
Frequency Range (Hz) 45~55 – 55~65
THDi <3%
Power Factor 1 lagging – 1 leading (Settable)
AC Connection 3W+N+PE
Transformer Ratio 270 / 400 270 / 400 270 / 400 315 / 400
Model CS100 CS150 CS250 CS500
Off Grid Specifications
Max. Output Power (kVA) 110 165 275 550
Rated Power (kW) 100 150 250 500
Rated Voltage (V) 400
Rated Current (A) 144 216 361 722
THDU ≤1% linear; or ≤5% nonlinear
Rated Frequency (Hz) 50 / 60
Overload Capacity 110% Continuous / 150% 10 sec
On to Off-grid Transfer Time 13ms
Model CS100 CS150 CS250 CS500
High Voltage PV Input ( Buck Mode)
PV Input Voltage Range (Voc)(V@25°C) 655-900 780-900
Max. PV Power (kW) MPPT in step of 60kW 120 / 180 / 240 120 / 180 / 240 300 / 360 600 / 660 / 720
MPPT Voltage Range(V@25°C) 544-747 648-747
buck mode Battery
Battery Voltage Range (V)  420-672 500-672
Battery cabinet Composition  Min 8 Max 12 Batteries Min 9 Max 12 Batteries
Max. Charging Power (kW) 120 / 180 / 240 120 / 180 / 240 300 / 360 600 / 660 / 720
Model CS100 CS150 CS250 CS500
General Data
Max On and Off grid parallel Units 10
Dimension W*D*H (mm)  1200*800*2050 1200*800*2050 (600*720*2050)*1+1200*800*2050 (600*720*2,050)*2+1600*1050*2050
Weight (kg) 1120 / 1150 / 1180 1250 / 1280/1310 1980 / 2010 3265/3295/3325
Operation Temperature (℃) -30~55
Relative Humidity 0~95% non-condensing
IP Rating IP20
Noise Emission (dB) <70
Altitude 4,000m (>3,000 Derating)
Cooling Forced Air Cooling
Display and Communication
Display LCD touch-screen / NooR Smart App
BMS Communication RS485, CAN
EMS Communication RS485, TCP/IP
Standards EN62109-1/-2, EN62447-1, EN61000-6-2, EN61000-6-4, South Africa NRS097-2-1:2017, Pakistan & India IEC62116, IEC61683

See warranty for performance warranty applicability.
See Performance Warranty Terms and the Standard Test Conditions “STC”.
All data is subjected to change without prior notice: Always ask WeCo for the most recent datasheet and manual before purchasing.
No part of this document can be copied or reproducted without WeCo written permission.

HYBO CS Boost HYBRID HYBO BUILT IN TRANSFORMER
PV Boost Mode
Model CS100 CS150 CS250 CS500
On Grid AC specifications
Max. Output power (kVA) 110 165 275 550
Rated Output Power (kW) 100 150 250 500
Rated Voltage (V) 400
Voltage Range (V) 320~460
Rated Current (A) 144 216 361 722
Rated Frequency (Hz) 50 / 60
Frequency Range (Hz) 45~55 -55~65
THDi <3%
Power Factor 1lagging -1leading (Settable)
AC Connection 3W+N+PE
Transformer Ratio 270 / 400 270 / 400 270 / 400 315 / 400
Model CS100 CS150 CS250 CS500
Off Grid Specifications
Max. Output Power (kVA) 110 165 275 550
Rated Power (kW) 100 150 250 500
Rated Voltage (V) 400
Rated Current (A) 144 216 361 722
THDU ≤1% linear; or ≤5% nonlinear
Rated Frequency (Hz) 50 / 60
Overload Capacity 110% Continuous / 150% 10 sec
On to Off-grid Transfer Time 13ms
Model CS100 CS150 CS250 CS500
High Voltage Battery Input ( Boost Mode)        
PV Input Voltage Range (Voc)@25°C 535-650
Max. PV Power (kW) 120 / 180 / 240 120 / 180 / 240 300 / 360 600 / 660 / 720
Boost mode Battery  
Battery Voltage Range (V) 624-850 624-850
Battery Cabinet Composition Min 11 Max 15 Batteries
boost mode Max. Charging Power (kW) 120 / 180 / 240 120 / 180 / 240 300 / 360 600 / 660 / 720
Model CS100 CS150 CS250 CS500
General Data
Max On and Off Grid Parallel Units 10
Dimension W*D*H (mm) 1200*800*2050 1200*800*2050 (600*720*2050)*1+1200*800*2050 (600*720*2,050)*2+1600*1050*2050
Weight (kg) 1120 / 1150 / 1180 1250 / 1280/1310 1980 / 2010 3265/3295/3325
Operation Temperature (℃) -30~55
Relative Humidity 0~95% non-condensing
IP Rating IP20
Noise Emission (dB) <70
Altitude 4,000m (>3,000 Derating)
Cooling Forced Air Cooling
Display and Communication
Display LCD touch-screen / NooR Smart App
BMS Communication RS485, CAN
EMS Communication RS485, TCP/IP
Standards EN62109-1/-2, EN62447-1, EN61000-6-2, EN61000-6-4, South Africa NRS097-2-1:2017, Pakistan & India IEC62116, IEC61683

See warranty for performance warranty applicability.
See Performance Warranty Terms and the Standard Test Conditions “STC”.
All data is subjected to change without prior notice: Always ask WeCo for the most recent datasheet and manual before purchasing.
No part of this document can be copied or reproducted without WeCo written permission.

Downloads